P&S 1597-HGW SELF-TEST GFCI HOS GRD RECEP 15A 1
P&S 1597-HGW SELF-TEST GFCI HOS GRD RECEP 15A 1
Stanion #1597HGWPS
MFG #1597HGW
UPC #785007036503
Product Overview
The new Pass & Seymour® hospital grade self-test GFCI receptacle with SafeLock™ protection conducts an automatic test every three seconds, ensuring it's always ready to protect. If the device fails the test, the indicator light flashes to signal that the GFCI should be replaced. It also has our proven SafeLock™ protection feature, if critical components are damaged and protection is lost, power to the receptacle is disconnected.
- Attributes
- Documents
- Application
- Includes
- Item Features
- Standards
BrandPass & Seymour®
Amperage Rating15 A
ColorWhite
Country of OriginCN
Dimensions1.03 in L x 1.73 in W x 4.2 in H
Frequency Rating60 Hz
GradeCommercial/Hospital
Horsepower1/2 hp
Manufacturer NameLegrand
MaterialThermoplastic
NEMA RatingNEMA 5-15R
Number of Poles2
Number of Wires3
Series1597HG
Temperature Rating-35 to 66 deg C
Terminal TypeBack/Side Wire
TypeDuplex Self-Test
Voltage Rating125 VAC
Industrial, Health Care, Education, Institutional, Retail, Office, Hospitality/Lodging and Multiple Dwelling, Commercial and Residential Applications
Matching TP26 Nylon Wallplate
- Class A rated GFCI
- Auto-ground clip assures a positive ground to metal box, meets 2015 UL requirements
- Thinner than competitor's GFCI receptacle, leaves more room for wires in the box
- Nylon face and body, 0.03 in brass contacts, 0.05 in zinc plated steel mounting strap, steel 8 to 32 terminal screws, steel hex head grounding screw
- Feed-through wiring configuration allows GFCI to protect downstream receptacles
- Prevents line load reversal miswire, no power to the face or downstream receptacles if wired incorrectly
- Side or internal screw pressure plate back wire with 14 to 10 AWG solid or stranded copper wire
- Ground screw has back wire clamp for easy installation, two back wire holes per terminal
- 10 kA short circuit rating, 102 to 132 VAC supply voltage range
- Mounting screws are shipped captive in the device and wallplate for easier installation
- Extra long strap, button colors match the device face, dual direction test and reset buttons
- Withstands 1500 VAC minimum dielectric, 4 to 6 mA trip level
- 0.025 s nominal trip time
- 95% maximum humidity
- 5 +/- 1 mA trip threshold, 20 A feed-through capacity
- Zinc-plated steel flat head mounting screws, nylon test/reset buttons, thermoplastic tamper-resistant shutter
- https://www.youtube.com/watch?v=wWKZUjGeZcA
CSA C22.2 No. 42/144|cULus Listed File No. E42190|Federal Specification W-C-596|FULs Listed|UL 943|UL 94 V-2 Flammability Rated