C-H PDG23M0030TFFL PDG2 3P 30A 65KA/480V FXFXTMT
Factory Availability
C-H PDG23M0030TFFL PDG2 3P 30A 65KA/480V FXFXTMT
Factory Availability
Stanion #PDG23M0030TFFLCH
MFG #PDG23M0030TFFL
UPC #786679859773
Product Overview
The Power Defense molded case circuit breaker portfolio is globally rated in a small footprint for easy adaptability no matter the application or project requirement. A circuit breaker with communicating electronic trip units and the ability to generate the data to help you optimize your facilities' performance, and to help keep your employees, customers and end-users safe by reducing the risk of arcflash events.
- Attributes
- Documents
- Application
- Item Features
- Standards
BrandEATON
Amperage Rating30 A
Auxiliary Contact Rating690 V
ColorWhite
Connection TypeLoad
Country of OriginDO
Dimensions6 in H x 4.1 in W x 3.5 in D
Enclosure TypeIP2X
Frame2
Frequency Rating50 to 60 Hz
Interrupt Rating65 kA
Manufacturer NameEaton
MaterialGlass Polyester
Mounting TypeFixed/Plug-In/DIN Rail
Number of Poles3
Power Rating3 W
SeriesPDG2
Temperature Rating-20 to +70 deg C
Trip TypeT-M (Fxd-Fxd) TU, Thermal Magnetic
TypePD2 Global Ratings
Voltage Rating600 V AC, 600 VAC
Wire Size14 to 1/0 AWG, 2.08 to 53.5 sq-mm
Marine Vessels and Equipment - Marine Vessels and Equipment - Other, Utility - Substations, Utility Transmission and Distribution, Aviation, Conventional Energy, On-Road Vehicles, Electrical Assemblies, Panels and EOEMs Applications, Panels and EOEMs , Renewable Energy and Alternative Energy Generation, Mobile Machinery and Equipment, Stationary Machine Equipment in Factory - Robotics, Vocational Vehicles
- Power Xpert Release trip units offer features such as Breaker Health, multiple Load Alarms, and Ground Fault Alarm to help avoid costly downtime through predictive and preventative maintenance
- Arcflash Reduction Maintenance System helps to reduce arc flash incident energy levels, thereby reducing PPE requirements and minimizing risk while improving personnel safety and productivity
- The PXR trip units provide an intuitive user interface that allows you to easily view and adjust breaker settings and system performance
- Embedded communications and metering help to reduce cost by eliminating the need for separate communication components and associated wiring
- Field installable components and trip units minimize the amount of inventory while enabling the user almost infinite options to customize the breaker to the application and their specification
- Thermomagnetic switch off technique
- 22 kAIC Icu at 125 VDC, 65 kAIC at 480V (UL), 22 kAIC Icu at 250 VDC, 50 kAIC Icu/ 40 kAIC Ics/ 105 kAIC Icm at 440V (IEC), 10 kAIC Icu/ 5 kAIC Ics/ 21 kAIC Icm at 690V (IEC), 50 kAIC Icu/ 30 kAIC Ics/ 105 kAIC Icm at 480V Brazil (IEC), 100 kAIC Icu/ 100 kAIC Ics/ 220 kAIC Icm at 240V (IEC), 100 kAIC at 240V (UL), 30/25 kAIC Icu/ 15/13 kAIC Ics at 525V South Africa (IEC), 35 kAIC at 600V (UL/CSA), 70 kAIC Icu/ 53 kAIC Ics/ 154 kAIC Icm at 380-415V (IEC) interrupt rating
CCC Marked,UL 489,IEC 60947-2,CSA,RoHS Compliant