EATON
C-H PDG23G0070TFFJ PDG2 3P 70A 35KA/480V FXFXTMT
Factory Availability
EATON
C-H PDG23G0070TFFJ PDG2 3P 70A 35KA/480V FXFXTMT
Factory Availability
Stanion #PDG23G0070TFFJCH
MFG #PDG23G0070TFFJ
UPC #786679222652
Product Overview
The Power Defense molded case circuit breaker portfolio is globally rated in a small footprint for easy adaptability no matter the application or project requirement. A circuit breaker with communicating electronic trip units and the ability to generate the data to help you optimize your facilities' performance, and to help keep your employees, customers and end-users safe by reducing the risk of arcflash events.
- Attributes
- Documents
- Application
- Item Features
- Standards
BrandEATON
Amperage Rating70 A
Auxiliary Contact Rating690 V
ColorWhite
Connection TypeLine/Load
Country of OriginDO
Dimensions6 in H x 4.1 in W x 3.5 in D
Enclosure TypeIP2X
Frame2
Frequency Rating50 to 60 Hz
Interrupt Rating35 kA
Manufacturer NameEaton
MaterialGlass Polyester
Mounting TypeFixed/Plug-In/DIN Rail
Number of Poles3
Power Rating3 W
SeriesPDG2
Temperature Rating-20 to +70 deg C
Trip TypeT-M (Fxd-Fxd) TU, Thermal Magnetic
TypePD2 Global Ratings
Voltage Rating600 V AC, 600 VAC
Wire Size14 to 1/0 AWG, 2.08 to 53.5 sq-mm
Utility - Substations, Utility Transmission and Distribution, Marine Vessels and Equipment - Marine Vessels and Equipment - Other, Electrical Assemblies, Panels and EOEMs Applications, Panels and EOEMs , On-Road Vehicles, Stationary Machine Equipment in Factory - Robotics, Renewable Energy and Alternative Energy Generation, Aviation, Mobile Machinery and Equipment, Conventional Energy, Vocational Vehicles
- Power Xpert Release trip units offer features such as Breaker Health, multiple Load Alarms, and Ground Fault Alarm to help avoid costly downtime through predictive and preventative maintenance
- Arcflash Reduction Maintenance System helps to reduce arc flash incident energy levels, thereby reducing PPE requirements and minimizing risk while improving personnel safety and productivity
- The PXR trip units provide an intuitive user interface that allows you to easily view and adjust breaker settings and system performance
- Embedded communications and metering help to reduce cost by eliminating the need for separate communication components and associated wiring
- Field installable components and trip units minimize the amount of inventory while enabling the user almost infinite options to customize the breaker to the application and their specification
- Thermomagnetic switch off technique
- 8 kAIC Icu/ 4 kAIC Ics/ 16.8 kAIC Icm at 690V (IEC), 18 kAIC at 600V (UL/CSA), 55 kAIC Icu/ 55 kAIC Ics/ 121 kAIC Icm at 240V (IEC), 10 kAIC Icu at 125 VDC, 36 kAIC Icu/ 36 kAIC Ics/ 75.6 kAIC Icm at 380-415V (IEC), 65 kAIC at 240V (UL), 10 kAIC Icu at 250 VDC, 25 kAIC Icu/ 20 kAIC Ics/ 52.5 kAIC Icm at 480V Brazil (IEC), 20 kAIC Icu/ 15/13 kAIC Ics/ 42 kAIC Icm at 525V South Africa (IEC), 30 kAIC Icu/ 22.5 kAIC Ics/ 63 kAIC Icm at 440V (IEC), 35 kAIC at 480V (UL) interrupt rating
IEC 60947-2,CSA,UL 489,CCC Marked,RoHS Compliant