SQD LR2K0310 TESYS K OVERLOAD RELAY CL10 2.6
SQD LR2K0310 TESYS K OVERLOAD RELAY CL10 2.6
Stanion #LR2K0310SQD
MFG #LR2K0310
UPC #3389110230499
Prop 65
Product Overview
TeSys K overload relays are designed to be used with TeSys K contactors to make a motor starter. These differential thermal overload relays detect over currents in the lines to the motor. When an overcurrent is detected the overload relay working with the contactor will disconnect the power to the motor. This will minimize the damage to the motor windings. This overload relay has an adjustable trip current rating of 2.6 to 3.7 amperes. This trip current rating is calibrated per Class 10A. Mounting on DIN rail, separated from the contactor, with use of a terminal block LA7K0064 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHs/Reach).
- Attributes
- Documents
- Application
- Item Features
- Standards
BrandSchneider Electric
Amperage Rating2.6 to 3.7 A
Contact Form1NC-1NO
Contact Rating3.7 A at 690 VAC
Country of OriginCZ, FR
Dimensions1.77 in W x 2.56 in D x 2.28 in H
Enclosure TypeIP2X
Frequency Rating0 to 400 Hz
Manufacturer NameSchneider Electric
Mounting TypeSurface
Number of Poles3
SeriesK-Line
Temperature Rating-20 to 55 deg C
Terminal TypeClamp/Threaded
TypeBi-Metallic
For TeSys™ K-LINE contactors applications
- It protects motors 1 5kW at 400V thanks to a thermal range 2 6-3 7A, a tripping class 10A and phase unbalance protection
- Ambient compensated
- Trip class 10 with single phase sensitivity
- Direct on under contactor mounting, plate with specific accessories, rail with specific accessories
- Manual or auto reset control type
RoHS Compliant|CE/CSA Certified|UL Listed|PROP65: This product can expose you to chemicals including: Antimony oxide and Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov