SQD LC1D093BL TESYS3PCTR9A AC3 4KW1NO1
SQD LC1D093BL TESYS3PCTR9A AC3 4KW1NO1
Stanion #LC1D093BLSQD
MFG #LC1D093BL
UPC #785901234326
Prop 65
Product Overview
TeSys Deca contactor, 3 poles (3NO), for motor control applications up to 9A/690V AC-3/3e (4kW@400V). They can be used to create motor starters for almost any type of application. It provides a low consumption 24V DC coil with transient suppressor module, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by spring terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (45mm width), DIN-rail mounting or screw fixing. Contactor is rated for 2HP at 200 to 208VAC, 2HP at 240VAC, 5HP at 480VAC and 7.5HP at 600VAC three phase. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine). Contactor is supplied with a low consumption 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as stanard. The NC contact is mirror certified. Spring terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.15 inches tall, 1.77 inches wide and 3.74 inches deep. It weighs 1.06 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards.
- Attributes
- Documents
- Application
- Item Features
- Standards
BrandSchneider Electric
Coil Power Rating2.4 W
Coil Voltage690 VAC, 24/300 VDC
Connection TypeSpring
Contact Configuration3NO
Contact Rating10/60 A at 600 VAC, 16/60 A at 600 VAC
Country of OriginID
Dimensions45 mm W x 95 mm D x 80 mm H
Enclosure TypeOpen
Frequency Rating50/60 Hz
Manufacturer NameSchneider Electric
Maximum Load Current9/25 A
Mounting TypeRail/Surface
Number of Auxiliary Contacts1NO-1NC
Number of Poles3
Operating Cycles3600 cycles/hr
Operating Temperature-5 to 60/-40 to 70 deg C
SeriesLC1D
Size45/80/95 mm
Terminal TypeSpring
TypeD-Line
Wattage0.2/1.56 W
For motor control and resistive loads
- 6 kV conforming to IEC 60947 rated impulse withstand voltage
- III overvoltage category
- 16 A at 140 deg F power circuit, 10 A at 140 deg F signaling circuit conventional-free air thermal current
- 250 A at 440 V power circuit conforming to IEC 60947, 140 A AC signaling circuit conforming to IEC 60947-5 1, 250 A DC signaling circuit conforming to IEC 60947-5 1 IRMS rated making capacity
- 250 A at 440 V power circuit conforming to IEC 60947 rated breaking capacity
- 20 A gG at 690 V coordination type 2 power circuit, 25 A gG at 690 V coordination type 1 power circuit, 10 A gG signaling circuit conforming to IEC 60947-5-1 associated fuse rating
- 2.5 MOhm at 50 Hz, Ith 25 A power circuit average impedance
- 65.45 to 88.55 ms closing and 20 to 30 ms opening operating time
- 3600 cycles/hr at 140 deg F operating rate
- Built-in bi-directional peak limiting diode suppressor coil technology
- 40 ms time constant
- 2.4 W at 68 deg F inrush power
- 2.4 W at 68 deg F hold-in power consumption
- 25 to 400 Hz signaling circuit frequency
- 5 mA minimum switching current
- 17 VAC signaling circuit minimum switching voltage
- 1.5 ms on energization between NC and NO contact/1.5 ms on de-energization between NC and NO contact non-overlap time
- >10 MOhm signaling circuit insulation-resistance
- TH protective treatment
- 3 deg of pollution
- https://www.youtube.com/embed/vlEODblcQoo
BV/GL//RINA Certified|CCC Certified|CE Certified|CSA C22.2 No.LR43364 Class 3211 04|DNV/GOST Approved|ECCN EAR99|EN 60947-4-1/60947-5-1|IEC 60647-4/60947-4-1/60947-5-1|PROP65: This product can expose you to chemicals including: Antimony oxide and Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65warnings.ca.gov|RoHS Compliant|UL File No. E164862 NLDX/508