SQD HJA261502 MOLDED CASE CIRCUIT BREAKER 600
SQD HJA261502 MOLDED CASE CIRCUIT BREAKER 600
Stanion #HJA261502SQD
MFG #HJA261502
UPC #785901939276
Prop 65
Product Overview
PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 25kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 150A, 2 pole, circuit breaker has a breaking capacity of 25kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an AC phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Attributes
- Documents
- Application
- Item Features
- Standards
BrandSquare D™
Actuator TypeToggle
Amperage Rating150 A
Connection TypeA-Line/Line/Load Lugs
Country of OriginUS
Dimensions9.73 in H x 2.94 in W x 4.8 in D
FrameH
Frequency Rating50/60 Hz
Interrupt Rating100 kA at 240 VAC/65 kA at 480 VAC/25 kA at 600 VAC/20 kA at 250 VDC
Manufacturer NameSchneider Electric
Mounting TypePlug-In/Unit
Number of Poles2
Phase1
Temperature Rating104 deg F
Trip Range900 to 1700 A
Trip TypeThermal Magnetic, Thermal/Magnetic
TypeType HJA
Voltage Rating600 V AC/250 V DC, 600 VAC/250 VDC
Wire Size14 to 3/0 AWG Al/Cu
Construction, Commercial Buildings, Oil and Gas, Control Equipment Panels, Marine, Industrial Buildings, Water Wastewater, OEM Commercial, Healthcare Facilities, Data Centers, Educational Campuses, Industrial Markets, Power Meters, Operating Assistance, Front Display Modules, Communication Networks, Overload and Short Circuit Protection
- Standard 80% or 100% rating
- Available in Unit mount, I-line or Drawout constructions
- A wide range of accessories, auxiliaries, and lug connections available
- https://www.youtube.com/embed/08co8m1vWjY
RoHS Compliant|UL 498 File No. E10027|CSA C22.2 No. 5-02 File No. LR40970|CCC/CE Marked|NMX J-266|Federal Specification W-C-375B/GEN|IEC 60947-2|NEMA AB1|NOM Certified|HACR Rated|PROP65: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.p65Warnings.ca.gov