SQD HDA36040 MOLDED CASE CIRCUIT BREAKER 600

SQD HDA36040 MOLDED CASE CIRCUIT BREAKER 600

Stanion #HDA36040SQD

MFG #HDA36040

UPC #785901419945
Prop 65

Stanion #HDA36040SQD

MFG #HDA36040

UPC #785901419945
Prop 65
Please register or log in to add items to your cart.
Product Overview
PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 40A, 3 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
BrandSquare D™
Amperage Rating40 A
Connection TypeI-Line™/Load Lug
Country of OriginCA, MX
Dimensions4.8 in L x 4.48 in W x 4.36 in D x 9.73 in H
FrameH
Frequency Rating50/60 Hz
Interrupt Rating25 kA at 240 VAC/18 kA at 480 VAC/14 kA at 600 VAC/20 kA at 250VDC
Manufacturer NameSchneider Electric
Mounting TypePlug-On
Number of Poles3
Phase3, 3 ph
Temperature Rating-13 to 158 deg F
Trip Range400 A Hold, 850 A
Trip TypeThermal Magnetic
Type80% Rated Type HDA
Voltage Rating600 VAC/250 VDC
Wire Size14 to 3/0 AWG