9012GAW5
Product Overview
The 9012G pressure switches are UL Listed and CSA certified as industrial control equipment. They are used to interface pneumatic or hydraulic systems with electrical control systems by opening or closing electrical contacts in response to pressure changes in the system. They have outstanding repeatability and drift performance. Their efficient design uses durable, low mass components for excellent performance under heavy duty vibration and shock conditions.
- Attributes
- Documents
- Application
- Item Features
- Standards
BrandSquare D™
Connection TypeScrew Clamp
Contact Configuration1NO-1NC/SPDT-DB
Contact Rating6 A at 120 VAC/0.27 A at 250 VDC
Country of OriginMX
Diaphragm MaterialNitrile
Differential6 to 30 psi
Dimensions3.5 in W x 2.63 in D x 5.55 in H
Enclosure TypeNEMA 4/4X/13
Housing MaterialAluminum
Manufacturer NameSchneider Electric
Maximum Pressure475 psi
Operating Cycles5000000 cycles
Pressure Rating3 to 150 psi
Temperature Rating-10 to 185 deg F
TypeElectro-Mechanical
Regulation Between 2 Thresholds Applications
- High shock-resistance
- High set point stability
- Internal or external range adjustment
- No drain line required
- Dual numerical range scale (psi and kPa)
- Nitrile diaphragms and zinc plated steel flanges are standard
- NC-NO, SPDT-DB, form Z, snap action, silver nickel contact
- Hydraulic oil (-40 to 250 deg F), non-corrosive liquid, air, non-corrosive gas controlled fluid
- 1/4 in 18 NPTF conforming to UL 508 fluid connection
- Regulation between 2 thresholds, adjustable scale
- 4 screw terminal block
- Screw clamp terminal, 22 to 12 AWG electrical connection
- Zinc plated steel flange
- Nitrile (Buna-N) diaphragm
- Die cast aluminum alloy 380, 120 operating cycles/min (maximum)
- 1/2 in NPT conduit entrance cable entry
- Watertight, dusttight, oiltight and corrosion-resistant (indoor/outdoor) environmental conditions
CCN NKPZ|CE Certified|CSA Class 3218 02 File No. LR26817|CSA LR25490 CLASS 3211 03|IEC Rated|PROP65: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65warnings.ca.gov|RoHS Compliant|UL 508-CSA C22.2 No 14-CE|UL E12158|UL File No. E12442 CCN NOWT