SOLA HS19B250 0.250KVA 120X240-12/24 BB
Product Overview
Buck-boost transformers are small, 1-phase, dry-type distribution transformers designed and shipped as insulating/isolating transformers. They have a dual voltage primary and a dual voltage secondary. These transformers can be connected for a wide range of voltage combinations. The most common use is to buck (lower) or boost (raise) the supply voltage a small amount, usually 5 to 27%. Buck-boost transformers are in compliance with NEC article 210.9, exception 1, when field connected as an autotransformer.
- Attributes
- Documents
- Application
- Item Features
- Standards
BrandSolaHD
Connection TypeCopper Lead Wire
Country of OriginVN
Dimensions4 in L x 4 in W x 8 in H
Enclosure TypeNEMA 3R
Frequency Rating60 Hz
Manufacturer NameEmerson Electric
Maximum Amperage Rating1.04/0.512 A Primary, 2.08/1.04 A Secondary
Phase1
Power Rating0.25 kVA
Primary Voltage120 x 240 V AC, 120 x 240 VAC
Secondary Voltage12/24 V AC, 12/24 VAC
SeriesHS19
TypeNon-Encapsulated
Hazardous Locations and Harsh Industrial Environment Applications
- Low cost, compact size and lightweight
- They are more efficient and cost less than equivalent isolation transformers
- They can handle loads up to 20 times the nameplate rating
- A buck-boost transformer is the ideal solution for changing line voltage by small amounts
- Conduit knockouts for side entry wiring
RoHS Compliant|UL 506|UL 1561|CSA C22.2 No. 47|CSA C22.2 No. 66|cULus File No. E25872|cULus File No. E77014