GE 306D002 STARTER STRTR 2 OP
Product Overview
GE full voltage (600 V maximum) magnetic motor starter has an encapsulated coil and a 3-leg overload relay to protect against overloads in all phases. It is on standard specifications of major manufacturers. The line offers features and benefits most asked for by users.
- Attributes
- Documents
- Application
- Item Features
BrandGE
Amperage Rating45 A
Coil Voltage110 VAC at 50 Hz, 115 to 120 VAC at 60 Hz
Connection TypePressure Screw Terminal
Dimensions9.12 in H x 5.44 in W x 5.5 in D
Enclosure TypeOpen
Frequency Rating50/60 Hz
Manufacturer NameABB
Number of Poles3
Operating Temperature-20 to 70 deg C
Overload Relay(2) 3 Leg Block Type Bimetal
Phase3
Reset TypeManual
SeriesCR306
TypeFull Voltage Non-Reversing Non-Combination
Voltage Rating600 VAC
Other
Electrical Distribution and Control Applications
- Tool less contactor disassembly (sizes 00 to 4) - allows quick access for inspection and maintenance
- Just release two retainers and pull a clip to get at magnet, coil and contacts
- Saddle clamp terminals (sizes 00 to 1) - accommodate ring, spade and stripped wire leads and carry permanent stamped in identification
- Staggered arrangement makes wiring easier and helps prevent shorting between phases
- Current carrying components - contact tips are weld-resistant silver cadmium oxide (fine silver on sizes 00 and 0 only)
- Contacts are installed in a wedge configuration for positive make with minimum bounce
- Class 20 overload protection
- Visual trip indicator with manual reset - to avoid surprise restarts, reset occurs on arm upstroke so a tripped condition can't be overridden by holding the arm down
- Manual weld check - provides a convenient test against welding of overload relay contacts, just depress the weld check operator to trip the relay, run a simple continuity test across the relay contacts, then depress the manual reset to return the starter to service
- Dual bimetals - anticipate overloads, responding to rising current and temperature with faster tripping on severe overloads for better motor protection, trip points are factory-calibrated for accuracy
- +/-10% trip adjustment - by turning a dial in the overload relay face allows tuning the protection to the motor on the spot
- Largest selection of modifications and accessory kits - includes auxiliary contacts, coils, fifth-pole addition, vertical and horizontal mechanical interlocks, surge suppressors, control circuit fusing, NEMA type enclosures, push buttons, selector switches, indicating lights, control transformers, space heaters and more
- List price includes a holding interlock, pressure terminals for the line and load connections, plus a 3-leg block type overload relay (manual reset)
- All enclosures include external reset