GE EP102ULC16 2P MCB-16A-C TRIP-10KA 480Y
Product Overview
ElfaPlus a miniature circuit breaker (MCB) designed and manufactured by GE (NYSE: GE), recently achieved an Underwriters Laboratories (UL) rating, making it a global MCB platform. Suitable for branch circuit device protection, the ElfaPlus platform offers a range of UL 489 and UL 1077 MCBs up to 63 A. With its dual UL and IEC certifications, original equipment manufacturers (OEMs) and panel builders can use the single ElfaPlus product platform whether their equipment is destined for the United States, Canada or another international market, explained Ricardo Cabal, senior product manager for GE energy connections Industrial Solutions. This not only simplifies design and testing costs, but also reduces customers stocking costs and space requirements while also streamlining their operations.
- Attributes
- Documents
- Application
- Item Features
- Standards
BrandGE
Actuator TypeToggle Handle
Amperage Rating16 A
Connection TypeWire/Busbar
Dimensions3.4 in H x 36 mm W x 2.7 in D
Enclosure TypeIP20/IP40
Frequency Rating50/60 Hz
Interrupt Rating10 kA
Manufacturer NameABB
Mounting TypeDIN Rail
Number of Poles2
SeriesEP100 UL E2000
Temperature Rating-13 to 131 deg F
Trip TypeThermal Magnetic
TypeCompact
Voltage Rating120/240 VAC
Wire Size14 to 2 AWG
Branch Circuit Protection, Convenience Receptable Circuit, Motor Control Circuit, Load Circuit Leaving the Equipment, HACR Equipment, Power Supplies, Control Instrumentation, Relays, UPS, Power Conditioners and Electrical Distribution Applications
- New modular compact standard 35 mm DIN rail mount UL
- Complete supplementary protection circuit breaker range of UL 1077 miniature circuit breakers up to 63 A current rating
- Module width of only 0.71 in (18 mm) per pole
- Contact position indication (red/green)
- Possibility for locking the toggle in OFF position
- Bi-functional (wires and bars) strong terminals
- The UL 10777 range can be connected with following UL 1077 extensions like auxiliary contacts, shunt trip and under voltage
- Suitable for secondary lines into OEM equipment's
ARRA Compliant|Buy American Act Compliant|RoHS Compliant|UL 1077|CSA C22.2 No. 235|EN/IEC 60947-2