SOLA E2HF225S 225KVA 480D-208Y 115C
Product Overview
SolaHD low temperature rise transformers feature a 220 deg C insulation system and temperature rise of only 80 deg C or 115 deg C under full nameplate load. Reduction in temperature rise increases reliability. The 35 deg C thermal reserve on 115 deg C rise units and 70 deg C reserve on 80 deg C rise units definitely mean higher reliability. The extra benefit is being able to operate either of these transformers as a 150 deg C rise unit and have a short term overload capacity of 15 to 30% without compromising normal life expectancy. Low temperature rise transformers are designed for any critical application requiring extra overload capability and cooler operating temperatures. All are available with either a 115 deg C or 80 deg C thermal rise and a class 220 deg C insulation system.
- Attributes
- Documents
- Application
- Item Features
- Standards
BrandSolaHD
Country of OriginUS
Dimensions36 in L x 24 in W x 46 in H
Efficiency98.95 %
Enclosure TypeNEMA 1
Frequency Rating60 Hz
Housing MaterialStainless Steel
Insulation220 deg C
Manufacturer NameEmerson Electric
Maximum Amperage Rating271/625 A
Mounting TypeFloor
Number of Taps7
Phase3
Power Rating225 kVA
Primary Voltage480 Delta V
Secondary Voltage208Y/120 V
Temperature Rating115 deg C
TypeDry Ventilated
Other
For any situation where the available voltage must be changed to accommodate the voltage required by the specific electrical circuit or connected equipment
- Extra thermal reserve
- Meets transit test requirements for ISTA test procedure 1E for packaged product
- Quiet operation with sound levels 3 to 6 dB below the NEMA ST-20 requirements
- 271 A primary, 625 A secondary amperage rating
ARRA Compliant|RoHS Compliant|UL File No. E25872|DOE 10 CFR p431|DOE 2016|UL 1561